The adiabatic compression that may occur when a valve is closed or opened in an uncontrolled manner or just the presence of compressed oxygen alone can lead to a combustion reaction.
This is relevant in particular to non-metallic material such as seals or lubricants. Modified Hy-Lok valves for use with compressed oxygen are available to reduce this type of risk for people and equipment. These valves have been approved by a Notified Body.
The special oxygen version of the 110 Series with ball seats manufactured out of modified PTFE (110 OS Series) allows compressed oxygen to be shut-off safely.
Pressure/temperature (oxygen): | Up to 69 bar (1,000 psi) at 60 °C (140 °F) |
Materials: | Stainless steel 316 |
Seat material: | Modified PTFE |
Wir helfen Ihnen gerne
Alle mit * gekennzeichneten Felder sind Pflichtfelder.
The special oxygen version of the T Series with ball seats manufactured out of modified PEEK (T OS Series) allows highly compressed oxygen to be shut-off safely.
T SERIES
Pressure/temperature (oxygen): | Up to 200 bar (2,900 psi) at 60 °C (140 °F) |
Materials: | Stainless steel 316 |
Seat material: | Modified PEEK |